TYPE
|
Portable, automatic, CVT turns-ratio tester
|
|
PHYSICAL SPECIFICATIONS
|
19.5" x 12" x 17" D (49.5 cm x 30.5 cm x 43.2 cm)
|
|
INPUT POWER
|
100 – 120 Vac or 220 – 240 Vac (selectable), 50/60 Hz
|
|
MEASUREMENT METHOD
|
ANSI/IEEE C57.12.90
|
|
RATIO-MEASURING RANGE
|
75 – 15,000 (5 digit resolution)
|
|
TURNS-RATIO ACCURACY
|
75 - 4,999: ±0.25%, 5,000 – 9,999: ±0.35%, 10,000 - 15,000: ±0.5%
|
|
PHASE ANGLE READING
|
0-360 degrees, ±0.2 degree accuracy
|
|
POLARITY
|
In-Phase or Out-of-Phase indication
|
|
TEST VOLTAGE
|
7440Vac @ 50ma
|
|
DISPLAY
|
Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels
|
|
COMPUTER INTERFACE
|
RS-232C
|
|
PC SOFTWARE
|
Windows XP/Vista/7 Transformer Analysis Software (included with purchase)
|
|
INTERNAL TEST RECORD STORAGE
|
128 test records. Each record contains 33 readings.
|
|
EXTERNAL TEST RECORD STORAGE
|
Up to 999 test records on external USB Flash drive.
|
|
SAFETY
|
Designed to meet IEC 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 Standards
|
|
ENVIRONMENT
|
Operating: -10?C to 50?C (15?F to +122?F)
Storage: (-30?C to 70?C (-22?F to +158?F)
|
|
HUMIDITY (MAX)
|
90% RH @ 40? C (104? F) non-condensing
|
|
ALTITUDE (MAX)
|
2000m (6562 ft) to full safety specifications
|
|
CABLES
|
One 50 ft. H cable, one 15 ft. X cable, one power cable, one safety ground cable
|
|
WARRANTY
|
One year on parts and labor
|
|
Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).
|